Luxtronik 2 is a heat pump controller used by several heat pump manufacturers. The Weble IoT Universal Gateway Luxtronik driver reads all the values and parameters of a Luxtronik 2 controller over the network, and writes the main parameters (operating modes, heating curve, hot water set point).
Driver key:
luxtronik— listed as Luxtronik under Building Automation in Gateway driver. Licence: required, contact support@weble.ch. Platforms: Linux and Windows.
8888 of the controller reachable from the box.8888 and Default polling ms/cron = 5000.You do not create addresses: the driver creates them from the first read, in two tabs.
The first read creates several hundred addresses, which are added one per second: the tables fill progressively over several minutes. This is normal.
Name, Cluster ID and Description are common to all drivers: see Gateways.
| Label | JSON key | Default | Description |
|---|---|---|---|
| Host | json.host |
192.168.1.99 |
IP address or host name of the Luxtronik 2 controller. Required. |
| Port | json.port |
8888 |
TCP port of the controller. |
| Default polling ms/cron | json.defaultPolling |
5000 |
Refresh period of the addresses that have no polling of their own: milliseconds, or a cron expression. 0 or empty: these addresses are not refreshed. |
Saving the gateway restarts the driver.
{
"host": "192.168.1.40",
"port": 8888,
"defaultPolling": 30000
}
%luxtronik:<property> — <property> is the name of a value or parameter of the controller.
| Address | Tab | Value |
|---|---|---|
%luxtronik:values |
Values | Object with all the values. |
%luxtronik:parameters |
Parameters | Object with all the parameters. |
%luxtronik:<value> |
Values | One value, for example temperature_outside. |
%luxtronik:<parameter> |
Parameters | One parameter, for example heating_operation_mode. |
%luxtronik:<parameter>_p |
Parameters | A parameter that has the same name as a value gets the suffix _p, for example temperature_hot_water_target_p. |
Examples:
%luxtronik:temperature_outside — outside temperature, °C.%luxtronik:temperature_hot_water — hot water temperature, °C.%luxtronik:heating_operation_mode — operating mode of the heating.A value that the controller does not use (option not installed) shows no.
| Label | JSON key | Default | Description |
|---|---|---|---|
| Polling ms/cron | json.polling |
(empty) | Refresh period of this address: milliseconds or cron expression. Empty: Default polling ms/cron of the gateway. |
| Description | description |
(empty) | Free text. |
| log | log |
never | Logging policy, see Log and Store value policies. |
| Property | Value |
|---|---|
| Readable | Yes — polled |
| Writable | Parameters accepted by the controller (see 4.2) |
| Created automatically | Yes — at the first read; addresses cannot be inserted, imported or deleted by hand |
| Routable | Yes |
| Loggable | Yes |
The controller returns all its values and parameters in one request. Each refresh therefore reads the whole controller, whatever the number of addresses due. A short polling on a single address sets, in practice, the refresh rate of the whole controller.
Keep the polling at 5 s or more. For trends and energy reports, 30 to 60 s is usually enough and keeps the load on the controller low.
After each write, the driver reads the controller again.
Write a value to a parameter address, from a route, the logic module or the API. The controller accepts writes on a defined list of parameters, among which:
| Address | Values |
|---|---|
%luxtronik:heating_operation_mode |
0 Automatic, 1 Second heat source, 2 Party, 3 Holidays, 4 Off |
%luxtronik:warmwater_operation_mode |
same values as above |
%luxtronik:cooling_operation_mode |
cooling mode |
%luxtronik:heating_curve_end_point |
20 to 70 °C |
%luxtronik:heating_curve_parallel_offset |
5 to 35 °C |
%luxtronik:deltaHeatingReduction |
-15 to 10 K |
%luxtronik:temperature_hot_water_target_p |
hot water set point, °C |
Temperatures outside the range are limited to the range. A write to a parameter that the controller does not accept fails with Wrong data.
Parameters change the behaviour of the heat pump. Agree the changes with the installer of the heat pump, and avoid writing the same parameter at a high rate (for example from a route that follows a fast-changing value).
Route a KNX or BACnet holiday switch to %luxtronik:heating_operation_mode with a route function that returns 3 when the switch is on and 0 when it is off.
Log %luxtronik:temperature_outside, %luxtronik:temperature_supply, %luxtronik:temperature_return and %luxtronik:temperature_hot_water with a 60 s gateway polling, and show them on a dashboard.
| Symptom | Cause | What to do |
|---|---|---|
Gateway restarts in a loop; log missing license |
No licence for the driver. | Add the licence in Gateways › License manager. |
Gateway does not start; log missing required config field: host |
Host is empty. | Enter the IP address of the controller. |
Log read from <host>:8888 failed: … (retry next poll) |
Controller unreachable or port closed. | Check the IP address, the network and port 8888. The driver logs recovered when reads work again. |
| Addresses appear slowly | First read: the addresses are added one per second. | Wait until the tables are complete. |
Write fails with Wrong data |
The parameter is not writable on the controller, or the value is not valid. | Use one of the parameters of 4.2 and a valid value. |
To read the driver log: open the gateway log (see Gateways).