Thies Clima weather stations for building automation measure brightness on three façades, twilight, temperature, humidity, wind speed and precipitation, and send them as telegrams on a serial line. The Weble IoT Universal Gateway Thies Clima driver receives these telegrams and turns each measurement into an address. The driver only listens: it sends nothing to the station.
Typical use: sun protection and blind control (brightness per façade, wind alarm, rain), and weather values for the HVAC.
Driver key:
thiesclima— listed as Thies Clima under Building Automation in Gateway driver. Licence: required, contact support@weble.ch. Platforms: Linux and Windows.
You do not create addresses. The driver creates %thiesclima:event at start, then one address per measurement when the first valid telegram arrives. Open the address table and check that the Value column updates at each telegram.
Name, Cluster ID and Description are common to all drivers: see Gateways.
| Label | JSON key | Default | Description |
|---|---|---|---|
| Serial Port | json.serialPort |
(empty) | Serial port or USB adapter connected to the station. |
| BaudRate | json.serialPortBaudRade |
9600 |
Line speed: 9600, 19200, 38400, 57600, 76800 or 115200. The JSON key is spelled serialPortBaudRade. |
| Parity | json.serialPortParity |
none |
none, even or odd. |
| Stopbit | json.serialPortStopBit |
1 |
1 or 2. |
| (JSON only) | json.serialPortDataBits |
8 |
Data bits. |
Saving the gateway restarts the driver.
{
"serialPort": "/dev/ttyUSB0",
"serialPortBaudRade": 9600,
"serialPortParity": "none",
"serialPortStopBit": 1
}
%thiesclima:event[/<value>[/<bit>]]
| Address | Value |
|---|---|
%thiesclima:event |
Object with all the values of the last telegram. |
%thiesclima:event/<value> |
One measurement, see 3.4. |
%thiesclima:event/status/<bit> |
One bit of the sensor status, see 3.4. |
Examples:
%thiesclima:event/brightnessSouth — brightness on the south façade, kLux.%thiesclima:event/windSpeed — wind speed, m/s.%thiesclima:event/precipitation — true while it rains.| Label | JSON key | Default | Description |
|---|---|---|---|
| Description | description |
(set by the driver) | Free text. |
| log | log |
never | Logging policy, see Log and Store value policies. |
| Property | Value |
|---|---|
| Readable | No — values are pushed by the station |
| Writable | No |
| Created automatically | Yes — on the first valid telegram |
| Routable | Yes |
| Loggable | Yes |
| Address | Description | Unit and range |
|---|---|---|
event/brightnessEast |
Brightness east | kLux, 0 to 150 |
event/brightnessSouth |
Brightness south | kLux, 0 to 150 |
event/brightnessWest |
Brightness west | kLux, 0 to 150 |
event/twilight |
Twilight | Lux, 0 to 250; 251 = above 250 Lux |
event/humidity |
Relative humidity | %, 0 to 100 |
event/temparature |
Temperature (the address is spelled temparature) |
°C |
event/windSpeed |
Wind speed | m/s, 0 to 40 |
event/precipitation |
Precipitation | true / false |
event/status |
Sensor status | object |
event/status/lowVoltage |
Low supply voltage | 0 / 1 |
event/status/heatingActivated |
Heating of the sensor on | 0 / 1 |
event/status/timeSynchronization |
Time synchronisation active | 0 / 1 |
event/status/lastTimeSynchronizationFailed |
Last time synchronisation failed | 0 / 1 |
event/status/hex |
Raw status | hexadecimal text |
A measurement that the station marks as invalid (field starting with ?) keeps the raw text sent by the station.
telegram checksum invalid, frame dropped.%thiesclima:event and every value and status address, creating them the first time.The refresh rate is the telegram rate of the station: it is set on the station, not on the box.
Route %thiesclima:event/windSpeed to the wind alarm object of the blind actuators, with a route function that returns 1 above 12 m/s and 0 below 8 m/s.
Route event/brightnessEast, event/brightnessSouth and event/brightnessWest to the KNX group addresses of the sun protection controller (multiply by 1000 if the controller expects Lux).
| Symptom | Cause | What to do |
|---|---|---|
Gateway restarts in a loop; log missing license |
No licence for the driver. | Add the licence in Gateways › License manager. |
Gateway does not start; log config error: serial port not found |
The serial port or USB adapter is not found. | Check Serial Port and the adapter. |
Only %thiesclima:event, no value |
No valid telegram received: wrong line settings, wiring, or station not sending automatically. | Check baud rate, parity, A/B wiring and the output mode of the station. |
Log telegram checksum invalid, frame dropped |
Disturbed line or wrong settings. | Check the line settings, the wiring and the termination. |
To read the driver log: open the gateway log (see Gateways).