An address is one data point of a gateway: a KNX group address, a Modbus register, a BACnet object property, an MQTT topic, an internal variable, a CPU metric… Every value that the device reads, writes, routes, logs or shows goes through an address. This page describes what is common to all drivers: the address table, the name and key forms, aliases, import and export. The fields specific to a protocol are described on the page of its driver (see Drivers).
Each address has:
1/2/3 for KNX or %M100 for Modbus);A name is unique only inside one gateway. Two gateways of the same protocol (two Modbus masters, two KNX lines) can each have an address
%M100or0/2/0. Read Address keys and Name collisions before you use a name that exists on several gateways.
In Gateways, click the name of a gateway. Its address table opens in a tab of the main panel. You can open the tables of several gateways side by side, for example to create a route by drag and drop (see Routes).
At the top of the table:
The columns depend on the driver. The following ones are common:
| Column | Content |
|---|---|
| Id | Numeric id of the address, unique on the device. Read-only. |
| Name | Address name, in the format of the driver. |
| Alias | Aliases of the address. Editable: see Aliases. |
| Status | Communication status of the address, as reported by the driver. |
| Status date | Date of the last status change. |
| Value | Last known value. Editable when the driver can write the address. |
| Value date | Date of the last value. |
| Store value | Policy that keeps the last value across restarts. See Log and Store value. |
| Log | Logging policy of the address. See Log and Store value. |
| Dashboard name | Label of the address in the dashboards. |
| Dashboard unit | Unit shown in the dashboards. |
| Routes | Number of routes that use the address. Click the number to open the routing table filtered on these routes. |
Unless the driver shows them, Id, Alias, Status, Status date, Dashboard name and Dashboard unit are hidden by default. Store value is shown as soon as one address of the gateway uses it, and Log as soon as a logger exists on the device.
To show or hide a column, open Live table › Columns and tick it. Click a column header to sort (hold Ctrl to sort on several columns), and use the column menu to filter.
The Live table menu changes the display:
| Entry | Effect |
|---|---|
| Live table | The default view. Values and statuses update in real time. When the driver groups its addresses in a tree, Expand all rows and Close all rows open or close every group. |
| Live table (flat view) | Same table without the tree: one line per address. Only offered for drivers that group their addresses. |
| Spreadsheet | A spreadsheet of the addresses, to edit many lines at once: copy and paste from Excel or LibreOffice, fill down, add lines. Administrators only. |
| Refresh table | In Spreadsheet mode, reloads the current addresses and discards the edits that were not saved. |
| Fullscreen | Shows the table on the whole screen. |
In Spreadsheet mode, nothing is written until you choose Save › All addresses or Save › Selected address. The device then compares the sheet with the gateway and opens the same dialog as an import (see Import a file): you choose whether to insert the new lines, update the existing addresses and remove the addresses that are no longer in the sheet.
The Log field of the form is only shown when at least one logger exists on the device (see Logging and history).
Many drivers also offer a scan, a discovery or a model import in their own menu (for example BACnet methods). See the driver page.
You do not always have to insert addresses yourself:
#cpu, #mem…), the VE.Direct driver (one address per field received), and others. See the driver page.$setpoint creates that address on an Internal gateway.To control which gateway receives the new address, prefix the name with the gateway: Internal¬$setpoint (see Address keys).
The device checks every new name against the name format of the driver. A name that does not match is refused with the message invalid address name "<name>" for driver <driver>. For example, an address of an Internal gateway must start with $: setpoint is refused, $setpoint is accepted.
Inserting a name that already exists on the same gateway is refused with address already exists.
Tick the lines to select them, or use the selection entries of the Selection menu (administrators):
| Entry | Effect |
|---|---|
| Update addresses | Opens one form for all the selected addresses. The fields you change are applied to all of them. |
| Remove addresses | Deletes the selected addresses, after a confirmation. |
| Read value | Asks the driver to read the selected addresses from the equipment now, after a confirmation. |
| Write value | Writes one value to all the selected addresses. Type the value (a number, a text or a JSON object) and confirm. |
| Download address | For drivers whose addresses hold files (for example the CSV export): downloads the content of the selected addresses, in one ZIP file. |
| Select all / Deselect all | Selects or deselects every address of the tab. |
| Select all filtered / Deselect all filtered | Selects or deselects only the addresses that match the current search and column filters. |
A right-click on a line opens the same actions for that address, plus Create route (a route with this address as source), Trace routes (listens to the routes that use the address, see Routes) and Resend value (writes the current value again, when the value is writable).
Export file saves the addresses of the current tab:
The file contains the name, the description, the log policy, the alias and every field of the driver form. The device asks whether to include the current values. The file is named after the device, the gateway, the address type and the date.
The CSV file is comma separated, with a header line. Fields of the driver configuration appear as dotted column names, for example json.remanent for Store value. Edit it in a spreadsheet and import it back to create or change many addresses at once.
Import file (administrators) reads a .csv or .json file with the same columns as an export. The gateway must be connected or stopped: an import is refused while it is in the pending state.
The device matches the lines of the file with the addresses of the gateway by name, then shows a summary:
| Option | Effect |
|---|---|
| Address to insert (n) | Names in the file that do not exist on the gateway. Tick to create them. |
| Address to update (n) | Names that exist on both sides. Tick to overwrite their configuration with the file. |
| Address to remove (n) | Addresses of this tab that are not in the file. Tick to delete them. |
| Import live values | Shown when the file contains values. Tick to write the values of the file too. Stored values (Store value) are always imported. |
The three action boxes are unticked by default: tick only what you want. When you import several files at once, Apply to all files reuses the same choices for each file.
Address to remove deletes every address of the tab that is missing from the file. Untick it when your file holds only a part of the addresses.
To copy a whole gateway (configuration and addresses) to another device, use the export and import of the gateway itself, in the ☰ menu of the gateway line (see Gateways).
The driver of a gateway imposes the format of its address names. Three examples:
| Driver | Example | Meaning |
|---|---|---|
| Internal | $counter |
Internal variable: always starts with $. |
| Modbus | %M2-100 |
Holding register 100 of unit (slave) 2. |
| KNX | 1/2/3 |
Group address 1/2/3. |
Most other drivers use a prefix of the form %<prefix>:, for example %mqtt:building/floor1/temp or %bac:… for BACnet. The prefix of each driver is listed in the driver reference, and the full syntax on the page of each driver.
Routes, logic gates, views and the API designate an address with a key. The following forms are accepted everywhere:
| Form | Example | Unique? |
|---|---|---|
| Numeric id | 23055 |
Yes, always. |
| Name | 4/7/25, %M1, $tempLiving |
Only inside one gateway. |
| Alias | tempLivingRoom |
No: several addresses can share an alias. |
| View identifier | an identifier computed by a view | No. |
| Gateway-scoped name | KNX-A¬0/2/0 or 12¬%M1 (gateway name or id, the ¬ character, then the name or alias) |
Yes. |
| Object (API) | { "name": "%M1", "gateway_id": 12 } or { "id": 23055 } |
Yes. |
When a text is given, the device looks for a name first, then for an alias, then for a view identifier.
When a name, an alias or a view identifier matches addresses on several gateways, a single address is used by the API calls (writeValue, readValue, getLastValue…), the Read gate and the Write gate without its Write to all option: the address of a connected gateway, otherwise the first one found. Which one is "first" is not guaranteed. Routes behave differently: see Name collisions.
To be sure to reach the right address, use the numeric id or a gateway-scoped key (
gateway¬name).
The ¬ character is not on most keyboards: copy it from this page, or type Alt Gr + 6 on a Swiss keyboard.
An alias is a free name that you give to an address, in addition to its protocol name. It makes routes and logic circuits easier to read (light_room_1 instead of 1/1/1) and portable between sites (the same circuit works on two sites where the wind speed is on different KNX addresses, as long as both addresses have the alias wind).
¬: the alias X¬Y¬Z gives the three aliases X, Y and Z.When several gateways have an address with the same name (for example %M100 on two Modbus gateways):
modbusA¬%M100) or give each address a different alias;gateway_id.Two settings of each address decide what the device keeps:
never or while no logger runs. See Logging and history.Both columns use the same policy editor (never, always, a period in milliseconds, on_change, …). The syntax and examples are on Log and Store value policies.
| Symptom | Check |
|---|---|
invalid address name "…" for driver … |
The name does not match the format of the driver. See Address name formats and the driver page. |
address already exists |
The name is already used on this gateway. Search for it in the table. |
| A route or a gate acts on the wrong gateway | The name exists on several gateways. Set the gateway in the route, or use gateway¬name. |
| The Log column or field is missing | No logger exists yet: create one in Loggers (see Logging and history). |
| Import file is refused | The gateway is in the pending state: wait until it is connected, or stop it, then import again. |
| The values stay empty | The gateway is not connected, or the driver cannot read the address: check the Status column and the gateway logs (see Logs and diagnostics). |