Matter is an IP-based smart home standard (Wi-Fi, Thread, Ethernet). The Weble IoT Universal Gateway Matter driver makes the gateway a Matter controller: devices are commissioned into the gateway's own fabric with their pairing code, then monitored directly on the local network, without a manufacturer cloud.
Typical use: bring the values of Matter sensors, plugs or switches into the gateway and route them to BACnet, MQTT, a logger or a dashboard.
Monitoring only. The driver receives the attribute values reported by the devices. It does not send commands to the devices and has no read on demand.
Driver key:
matter— listed as Matter under Building Automation in Gateway driver. Licence: not required. Platforms: Linux and Windows.
MT:.MT:…) and click Commission. Commissioning can take a few minutes. When it succeeds, the message Node <id> commissioned shows the node ID given to the device.%matter: prefix, for example %matter:kitchen-plug.
Name, Cluster ID and Description are common to all drivers: see Gateways. The Matter driver has no other parameter.
The fabric of the gateway (its certificates) and the list of commissioned devices are stored in the data directory of the box, under the gateway ID. They belong to this gateway:
The gateway needs no setting in json:
{}
%matter:<label>[/<endpoint>/<cluster>/<attribute>]
| Part | Meaning | Values |
|---|---|---|
<label> |
Free label of the device, chosen when you insert the device address. | Any text without /. |
<endpoint> |
Endpoint number of the device. | Number, given by the device. |
<cluster> |
Name of the Matter cluster. | As reported by the device. |
<attribute> |
Name of the attribute. | As reported by the device. |
Examples:
%matter:kitchen-plug — device address, linked to a node by Node ID%matter:kitchen-plug/1/<cluster>/<attribute> — an attribute of endpoint 1 of the plug, for example its on/off state, created by the driverThe cluster and attribute names are the ones given by the Matter library; the description of a created address is <cluster>.<attribute>. Values are emitted as reported by the device, without scaling: check the unit of the attribute in the device documentation and convert it in a route function if needed.
| Label | JSON key | Default | Description |
|---|---|---|---|
| Name | name |
%matter: |
Device address: %matter:<label>. |
| Node ID | json.nodeId |
(empty) | Node ID of the commissioned device. Shown only on a device address. Click the magnifier to pick it in the list of commissioned nodes. |
Log works the same way for every driver: see Log and Store value policies.
| Property | Value |
|---|---|
| Readable | No read on demand. Attribute addresses receive the values reported by the device. |
| Writable | No |
| Created automatically | Attribute addresses: yes, when the device reports the attribute. Device addresses: no, insert them by hand. |
| Routable | Yes |
| Loggable | Yes |
The driver connects to the nodes linked to device addresses when it starts. After inserting a device address, or after changing its Node ID, restart the gateway.
Right-click a device address and choose Decommission device, then confirm Remove this device from the gateway fabric?
Device not reachable: it was removed from the gateway only. Reset it before pairing it again. is shown. Reset the device to factory settings before commissioning it again.Deleting the address does not decommission the device.
%matter:meeting-room-plug with its Node ID; restart the gateway.%matter:meeting-room-plug/<endpoint>/.Insert %matter:office-sensor linked to the sensor and restart. When the temperature attribute appears under it, route it to an Internal address, with a function that converts the value to °C if the device sends another unit, and log that address.
| Symptom | Cause | What to do |
|---|---|---|
| Commissioning fails | The device is not reachable on the IP network, the code is wrong, or the device is already in another fabric and not in pairing mode. | Check that the device is on the same network as the gateway, enter the code again, open the pairing window from the app that already controls the device, or reset the device. |
Message Matter commission timed out, the result is unknown: check List nodes |
Commissioning took more than 5 minutes. | Open List nodes: the node may have been commissioned anyway. |
Matter controller not started |
The controller did not start (see the gateway log). | Read the log, then restart the gateway. |
| A device address receives nothing | The gateway was not restarted after the address was added, the Node ID is wrong, or the device is offline. | Restart the gateway; check the Node ID with List nodes. |
| All devices lost after the gateway was deleted | The fabric is stored under the gateway ID. | Reset the devices and commission them on the new gateway. |
To read the driver log: open the gateway log (see Gateways and Logs and diagnostics).